Troubleshooting
Common failure modes with their diagnostic signatures and fixes.
Reading The Logs
All log lines are written to stderr and do not appear on stdout. The ADPP framed-stdio transport uses stdout exclusively, so logs are always safe to redirect or capture separately.
| Prefix | Stream | Meaning |
|---|---|---|
[INFO] | stderr | Normal progress and startup events |
[WARN] | stderr | Recoverable failure or degraded state |
[ERROR] | stderr | Fatal failure or unrecoverable condition |
Provider Fails To Start
Config parse error
The provider exits with code 1 before opening the bus.
[ERROR] <yaml exception or "required field missing: ..." message>Use --check-config to validate before running:
./anolis-provider-bread --check-config config/example.local.yamlA valid config prints [INFO] Config valid: ... and exits with code 0.
Bus open failure
Hardware builds only (ANOLIS_PROVIDER_BREAD_ENABLE_HARDWARE=ON). The provider exits with code 1 after loading config.
[ERROR] open failed code=TransportError attempts=1 message="failed to open Linux I2C bus '/dev/i2c-1'"Check that the bus path exists and the process has permission:
ls -la /dev/i2c-*
sudo setfacl -m u:$USER:rw /dev/i2c-1 # or run as root temporarily during devConfirm hardware.bus_path in your config matches the actual device node.
Required live session on no-hardware build
If config sets hardware.require_live_session: true but the provider binary was built with ANOLIS_PROVIDER_BREAD_ENABLE_HARDWARE=OFF, startup fails immediately:
[ERROR] hardware.require_live_session=true but provider was built without hardware support ...Fix by rebuilding with a Linux hardware preset:
cmake --preset dev-linux-hardware-release
cmake --build --preset dev-linux-hardware-releaseDevice Not Responding During Startup
The probe sequence runs once at startup. A device that fails any probe step is excluded from the inventory.
Version query fails (timeout or transport error)
[ERROR] query_read failed addr=0x08 code=TransportError attempts=3 native_code=-5 message="..."
[WARN] probe 0x08 version failed: <message>
[WARN] 1 unsupported or incompatible probe(s) excluded from inventory
[WARN] excluded 0x08 status=VersionReadFailed detail=version query failed: ...The [ERROR] line is the raw CRUMBS session failure. The [WARN] lines are the higher-level probe summary.
Common causes:
- Wrong I2C address in
discovery.addresses - Device not powered or not wired
hardware.query_delay_ustoo low for the device to prepare its reply
Try increasing query_delay_us (default 10 000 µs). On a working device this probe always succeeds.
Unexpected version reply opcode
[WARN] probe 0x08 unexpected version reply opcode 0xNNThe device responded but returned an unexpected opcode. Most likely cause is a bus collision or a non-BREAD device at that address.
Unknown BREAD type ID
[INFO] probe 0x08 unsupported type_id 0x05
[WARN] excluded 0x08 status=UnsupportedType detail=unknown BREAD type_id: 0x05The device probed successfully but its type is not supported by this provider version. This is not a wiring issue; it is a firmware/software mismatch. Either update the provider to support the new type or remove the address from the config.
Version Mismatch
Version compatibility is checked after a successful version query. A mismatch excludes the device from the inventory.
[WARN] probe 0x08 compat failed: <detail>
[WARN] excluded 0x08 status=IncompatibleCrumbsVersion detail=...The status field indicates what was incompatible:
| Status | Meaning | Fix |
|---|---|---|
IncompatibleCrumbsVersion | Device firmware uses a CRUMBS version older than the minimum required by bread-crumbs-contracts | Update device firmware |
IncompatibleModuleMajor | Module major version mismatch (breaking change) | Update firmware to match the contracts version expected by this provider |
IncompatibleModuleMinor | Module minor version below required minimum | Update firmware |
The exact minimum versions expected are defined in bread-crumbs-contracts.
GET_CAPS Failure — Baseline Fallback
If the capability query (opcode 0x7F) fails or returns a parse error, the provider falls back to the baseline capability profile for that device type.
[WARN] probe 0x08 caps query failed (timeout), using baseline fallbackor after a successful caps response that cannot be parsed:
[WARN] probe 0x08 caps parse failed, using baseline fallbackThe device is still added to the inventory. The impact depends on the device type:
| Device | Baseline flags | Practical impact |
|---|---|---|
| RLHT | All flags set | No impact, full function set available |
| DCMT | OPEN_LOOP | BRAKE_CONTROL only | Closed-loop control functions absent from DescribeDevice |
For DCMT, falling back to baseline means set_speed_closed_loop and related closed-loop functions are not exposed until a successful caps query can confirm the device supports them.
If caps queries fail intermittently, check for I2C bus contention or try increasing hardware.query_delay_us.
Expected Device Absent — Provider Degraded
When a config devices: entry specifies an id and address but the device is not found or excluded during startup, the provider enters a degraded state.
[WARN] 1 expected device(s) not found in inventory
[WARN] missing expected device id=dcmt0GetHealth returns:
provider.state = STATE_DEGRADED
provider.message = "provider ready but 1 expected device(s) not found"Per missing device:
device_health.device_id = "dcmt0"
device_health.state = STATE_UNREACHABLE
device_health.message = "expected device not found during startup"WaitReady still completes — the provider is technically ready — but GetHealth reflects the reduced inventory.
Common causes:
- Hardware not plugged in or not powered
- Mismatch between
addressin config and actual I2C address on the bus - Device excluded due to a probe failure (check for earlier
[WARN]or[ERROR]lines at the same address)
Fix: correct the devices: list in the config or resolve the underlying hardware issue.
Runtime Read And Call Failures
Hardware faults during normal operation are now surfaced on stderr.
read_signals failure
[ERROR] query_read failed addr=0x08 code=Timeout attempts=3 native_code=-110 message="..."
[WARN] read_signals device='rlht0' failed: <message>The ADPP client receives an error status on the ReadSignals RPC. The provider stays running.
call failure
[ERROR] query_write failed addr=0x09 code=TransportError attempts=3 native_code=-5 message="..."
[WARN] call device='dcmt0' fn='set_speed_open_loop' failed: <message>The ADPP client receives an error status on the Call RPC.
Common session error codes and fixes
| Code | Meaning | Fix |
|---|---|---|
Timeout | Device did not respond within timeout_ms | Increase hardware.timeout_ms; check device power |
TransportError | I2C bus-level error (EIO, ENXIO, etc.) | Check wiring, check I2C pull-ups, check bus speed |
CrcError | CRUMBS frame CRC mismatch | EMI or loose connection; check I2C signal quality |
AlreadyOpen | Session open called twice | Provider logic error; should not occur in normal use |
Persistent errors from a previously healthy device usually indicate a hardware or wiring fault. Isolated errors that self-resolve are consistent with I2C bus transients; tuning query_delay_us can help.
Checking Runtime Health
The GetHealth RPC returns a snapshot. Key fields:
provider.metrics["device_count"] — number of devices in inventory
provider.metrics["degraded"] — "true" if any expected device missing
provider.metrics["unsupported_probe_count"] — probes excluded at startup
provider.metrics["inventory_mode"] — "hardware" or "config-seeded"In no-hardware builds (ANOLIS_PROVIDER_BREAD_ENABLE_HARDWARE=OFF), inventory_mode will be config-seeded and no I2C activity occurs. All probe-related warnings and errors are hardware-path only.